电气工程与电子技术学报

A Practical Soil Resistivity Electrical Earthing Investigation: Ile-Ife, Nigeria

Apena WO, Ale TO, Oyetunji SA and Ihiabe YA

Electrical earthing design surge protection relies on accurate determination of soil resistivity down the vertical soil profile. The study investigated soil resistivity of a rocky region in Ile-Ife, Nigeria, were wenner method claimed to be failed. Pole-pole and Schlumberger electrode configurations method were deployed and electrical resistivity (ER) methods involving both horizontal profiling (HP) and Vertical Electrical Resistivity (VES) using an intelligent machine – ABM 300 C. Measurements were made along seven traverses to revealed soil resistivity variation in the region. Forty-eight VES stations were occupied along the traverse using the Schlumberger array with electrodes spacing of (AB/2) varying from 1 to 60 m. The vertical electrical sounding data were interpreted quantitatively by partial curve matching and iterative modelling using WinglinkTM software. Geoelectric sections were generated on each of the traverses using the VES interpretation results. The result of this research revealed variation down the layers (profile). The resistivity ranges from 30 Ohms-m to 4893 Ohms-m and the thickness from 0.44 m to 13.7 m within the conductive layers respectively.

免责声明: 此摘要通过人工智能工具翻译,尚未经过审核或验证